VFD to spindle wiring diagram
One schematic covering power, earth, brake resistor, run/stop control and speed reference — plus the five wiring mistakes that account for most dead drives.
Power and earth
Supply VFD Spindle
────── ─── ───────
L (live) ───────────► L1 / R
N (neutral)───────────► L2 / S
PE (earth) ────┬──────► PE ──────────────────────► frame / earth pin
│ │
└──────────────────────────────────────────┘ (bonded, low impedance)
U ─────────────────────────► U
V ─────────────────────────► V
W ─────────────────────────► W
(screened 4-core: 3 phases + PE, screen clamped at the drive end)
B1 ────┐
B2 ────┴──[ braking resistor ]── (only if fitted)
Substitute L1/L2/L3 for L1/L2 if you have three-phase in. Nothing else
about the power wiring changes. The output is still three phases.
Control and speed reference
VFD Controller / panel ─── ────────────────── FOR ──────[ relay or switch ]────── spindle on REV ──────[ relay or switch ]────── reverse (optional) COM ─────────────────────────────── common for the above AI1 ◄───── 0–10 V analogue ─────── spindle speed command GND ◄───── analogue 0 V ─────── reference for AI1 (NOT chassis earth) +10V ─────► potentiometer top ────── only for a manual pot GND ─────► potentiometer bottom AI1 ◄───── potentiometer wiper FA / FB ───[ fault relay ]────────── to an E-stop chain or indicator
Analog ground and protective earth are different things. Joining them at the wrong point is a reliable way to inject noise into the speed reference — the spindle speed will wander or jump when the drive switches.
Five mistakes, in the order they happen
| Mistake | What you see | Cost |
|---|---|---|
| Supply landed on U/V/W | Nothing, then a bang, then nothing | Drive is scrap |
| Earth not carried to the spindle frame | Works, until someone touches the frame | Safety, and a noise floor you cannot debug |
| Screen floating or earthed at the spindle end only | Works, but USB/limits drop out under load | Hours of chasing the wrong fault |
| Brake resistor on the wrong terminals | Overvoltage trip on decel, or a short across the bus | Drive or resistor |
| Output switched by a contactor | Works a few times, then an output fault | Drive |
Sizing the protective conductor
The earth conductor has to be able to carry a fault current long enough for the supply protection to operate, so it is normally specified at least as large as the phase conductors on small drives, and by code above that. Use the sizing calculator for the phase conductor size and match the earth to it as a minimum. Local wiring rules override anything here.
Checking the work before power
- Supply disconnected. Continuity from the supply plug's earth pin to the VFD chassis and to the spindle frame: should be near zero ohms.
- Continuity from each of U, V and W to the spindle frame: should be open (or megohms if you have an insulation tester, with the drive disconnected).
- Resistance U–V, V–W, W–U: three roughly equal, low readings.
- Control wiring: nothing except intended dry contacts across FOR/COM. No voltage sources.
- Brake resistor: measured resistance equal to what is printed on it, and not below the drive's stated minimum.
Parts
Connectors and cable
Control parts
Questions
Where does the brake resistor go?
Across the drive's DC bus terminals, never on the output. The terminals are usually marked with a + and a brake or B designation — confirm them in your manual, because the letter is not standard.
How do I wire the 0–10 V speed reference?
Analogue reference and analogue common, on a screened twisted pair, routed away from the motor cable. Noise on this pair is the single most common cause of speed that wanders under load.
How big does the earth conductor need to be?
Sized for the prospective fault current of the supply, not for the spindle's load current. On long runs it goes up with the phase conductors rather than staying small.
Sources and method
Three kinds of statement appear on this page, and each is labelled where it occurs:
- Derived — the schematic is the conventional one; terminal labels are given by function because the printed labels differ between makers.
- Rule of thumb — workshop practice, not a standard. Given with the range it is meant to hold over, and it loses to your manual wherever the two disagree.
- Maker-specific — parameter numbers, connector pin numbers, minimum brake resistance, maximum cable length, bearing speed limits. Not published here. They move between firmware revisions of the same model, and a wrong one is worse than none.
Standards and documents
- IEC 61800-5-1 — adjustable speed drives: safety requirements
- IEC 60204-1 — electrical equipment of machines
- IEC 61000-6-2 — EMC immunity for industrial environments
- The manual for your own drive and spindle — the only valid source for maker-specific values