VFD sizing calculator
Put the spindle nameplate in, get the drive current class, the supply current and a cable size out. Every number is derived on the page, and every maker-specific value is deliberately left for your own manual.
Size a drive from a spindle nameplate
Leave rated current blank if the nameplate does not give it — it will be estimated from power, voltage, power factor and efficiency.
What it does and does not do
Does: turns nameplate power into a current, applies your margin, checks your supply against your spindle voltage, and estimates what the supply circuit has to carry.
Does not: know your drive's derating curve, your ambient temperature, your altitude, or your local wiring rules. A calculator that pretended to would be giving you a number you could not defend.
The two numbers that decide everything
- Rated current. The drive's continuous output current rating must exceed it. Read why current beats kilowatts.
- Rated voltage. Must match the drive's output class. No amount of margin fixes a mismatch.
Worked example: 2.2 kW, 220 V, single-phase 230 V supply
Take a common water-cooled router spindle: 2.2 kW, 220 V three-phase, no rated current on the plate, running to 400 Hz.
- Estimate the current. With cosφ = 0.85 and η = 0.85:
I = 2200 / (√3 × 220 × 0.85 × 0.85) ≈ 8.0 A. That is the figure a nameplate would confirm or correct — and if the plate says something materially different, the plate wins. - Apply the margin. At 20 %, the drive needs to offer at least about 9.6 A continuous output. Note what that does to the shopping: plenty of drives labelled “2.2 kW” are rated below 9.6 A on the output, because their label assumes a standard motor at 50 Hz.
- Size the supply. On a single-phase 230 V input the supply current is
roughly
√3 × 8.0 ≈ 13.9 A, before drive losses. Design the circuit for more than that, not for 2.2 kW divided by 230 V. - Sanity-check the voltage. A single-phase 230 V input gives about 230 V out, which matches a 220 V winding. If this spindle had been the 380 V version, step four would have failed and the fix would have been a different spindle, a relinkable winding, or a transformer — not a bigger drive.
- Then check the derating. The spindle lives at 400 Hz, permanently above base frequency. Whatever the drive's nameplate says, look for its continuous current at that output frequency.
After you have the number
- Check the drive's specification for continuous output current at your ambient temperature, and specifically any derating above base frequency.
- Check the maximum output frequency actually reaches what you need — see the speed page for what frequency your target rpm requires.
- If you need a fast stop, size the braking resistor too.
- Wire it as shown in the wiring diagram.
Parts
Drives
Questions
Should I size the drive on kW or on current?
On current. Drives are rated by output current, and the current your spindle draws depends on its voltage and efficiency, not on the power figure alone.
How much margin should I leave?
Enough that the drive is not sitting at its continuous rating at full load, and more again if you are feeding it from a single-phase supply. The calculator shows both cases.
Can an oversized drive hurt?
It costs more and it will not protect a small spindle as tightly, but electrically it is safe. An undersized drive trips under load — usually with a code that looks like something else.
Sources and method
Three kinds of statement appear on this page, and each is labelled where it occurs:
- Derived — every number is computed from what you type, and the formulae are printed next to the results so you can check them.
- Rule of thumb — workshop practice, not a standard. Given with the range it is meant to hold over, and it loses to your manual wherever the two disagree.
- Maker-specific — parameter numbers, connector pin numbers, minimum brake resistance, maximum cable length, bearing speed limits. Not published here. They move between firmware revisions of the same model, and a wrong one is worse than none.
Standards and documents
- IEC 61800-2 — adjustable speed drives: rating specifications
- NEMA MG 1 — motors and generators
- IEC 60034-1 — rotating electrical machines
- The manual for your own drive and spindle — the only valid source for maker-specific values