VFD fault codes: what the drive is telling you

Drives display a code; most people read it as a model-specific mystery. Grouped by what the drive is actually measuring, almost every fault resolves into one of six physical conditions — and the diagnosis is the same whatever the label says.

We do not publish a code table. The same condition is OC, E-OC, OC1 or Err 04 depending on make, model and firmware. Look up what your own drive calls each condition in its manual, then use this page to work out what to check.

The six conditions

Grouped by what is measured, not by what the display says
ConditionThe drive measuredCheck, in order
OvercurrentOutput current past the limitAcceleration time too short · rated voltage or current parameter wrong · a short or earth fault on the output · a contactor switching the output
OvervoltageDC bus too highDeceleration time too short · no brake resistor or one too high in ohms · supply voltage genuinely high
UndervoltageDC bus too lowSupply missing or a phase missing · loose terminal · undersized supply cable · supply dip on acceleration
OverloadSustained current above the motor's rating for long enoughRated current parameter too low · genuine mechanical overload · duty too aggressive · cooling failed
OverheatDrive's own heatsink temperatureFan failed · no clearance around the drive · cabinet too hot · carrier frequency set high
Earth faultCurrent leaving on the earth conductorA winding earthed · cable damaged · moisture in the connector · screen incorrectly bonded

The classic: trips with nothing on the spindle

This one gets its own section because it is the most common first-power-up experience and it is almost never a hardware fault.

If the drive trips the moment you command a run, with no tool fitted and the spindle spinning freely, then mechanical overload is impossible by definition. What is left:

  1. Rated voltage parameter wrong — too low and the motor cannot make flux and draws excessive current; too high and it saturates.
  2. Rated current parameter wrong — too low and the protection fires on normal magnetising current.
  3. Acceleration time far too short — the spindle has inertia even with nothing in the collet.
  4. Output frequency far above what the parameters expect, putting the motor into a region the V/f curve was not set up for.
Fix: restore factory defaults, re-enter the five motor parameters from the nameplate, then set the acceleration time generously and reduce it later. See the parameter page for the commissioning order.

The second classic: overvoltage every time you stop

Energy has nowhere to go. Your options, in the order to try them:

  1. Lengthen the deceleration time. Free, and often sufficient.
  2. Fit a braking resistor sized against the drive's minimum resistance.
  3. If it still trips, the demanded stop is faster than the resistor can absorb — lengthen the deceleration time rather than reducing the resistance.

Before you blame the drive

Rule these out first; they cost nothing and they account for a large share of “faults”:

Resetting is not fixing

Most drives will let you define an automatic restart after a fault. That is a useful feature on a production machine with a known intermittent cause and a bad idea on a machine you are still commissioning. A drive that silently restarts into a fault condition will eventually restart into the one that was a real earth fault.

Find the cause first. Automate the restart afterwards, if you still want to.

Parts

Control and test parts

Questions

My drive trips immediately with nothing on the spindle. What does that mean?

Most often it is not the spindle: a short or earth fault in the cable, a brake resistor on the wrong terminals, or a control input not in the state the drive expects.

Why does it trip on overvoltage every time I stop?

The spindle is regenerating into the DC bus with nowhere for the energy to go. Lengthen the deceleration time or fit a braking resistor.

Is resetting the fault a fix?

No. A fault code tells you which protection operated, not what caused it. Clearing it without finding the cause just means it will come back, usually at a worse moment.

Sources and method

Three kinds of statement appear on this page, and each is labelled where it occurs:

Standards and documents

Further reading