Cable voltage drop calculator

How much of your supply voltage is lost in the cable before it reaches the spindle, and how much of it turns into heat on the way. Everything here comes from the resistivity of the metal — no tables, no maker data.

The calculation

Voltage drop in a run

Length is the one-way distance, not the total copper you buy. Cross-section is per conductor.

What the number means

Three numbers come out, and they answer three different questions:

The table below holds the current and the length fixed and walks through standard conductor sizes, which is usually the faster way to answer "is my cable too thin" — you are rarely choosing the length, and you are often choosing the cable.

On the output side of a VFD

The calculation above is a DC-resistance calculation. It is sound for the supply side of the drive, where the cable carries 50 or 60 Hz. The output side is not 50 Hz — it is a PWM waveform at the drive's carrier frequency, and two things stop being negligible there:

Both make the real situation worse than the number printed here, in the same direction — so the result is a floor, not a ceiling, for the motor side. This is also why this page does not publish a maximum cable length. The figure depends on the drive's carrier frequency, the insulation system of your particular spindle, and whether you have fitted an output reactor or a dV/dt filter. Those are all maker-specific, and a single number borrowed from another machine is worse than no number. Read cables, reactors and filters for what actually mitigates it.

What is safe to conclude from this page. If the drop is already large on DC resistance alone, no filter will save the installation — go up a conductor size. If the drop is small, the supply side is fine and any remaining problem on a long motor run is a high-frequency problem, which is a different fix.

When it matters and when it does not

Parts

Shielded cable & connectors

Questions

Is this the same as the maximum cable length a maker publishes?

No, and this site deliberately does not publish that number. It depends on your drive's carrier frequency, the insulation system of your spindle and whether you have fitted an output reactor or filter — all maker-specific.

Why does the real drop on the motor side come out higher than this?

Because the drive output is PWM at the carrier frequency, not 50 Hz. Skin effect raises the effective resistance and the cable's own inductance and capacitance start to matter, so the figure here is a floor for the motor side.

What do I do if the drop is too large?

Go up a conductor size — that is the only fix that reduces resistive drop. If the drop is small and a long motor run still misbehaves, it is a high-frequency problem, and reactors and filters are the answer rather than thicker copper.

Sources and method