VFDSPINDLE VFD & CNC spindle wiring, sizing and setup

Braking resistors: when you need one and how to size it

A VFD cannot push energy back into the supply. When you ask a spinning spindle to slow down, that energy goes into the DC bus capacitor, the bus voltage rises, and the drive trips on overvoltage. A braking resistor is where the energy goes instead.

Do you need one?

Router spindles are light for their power and are often fine without one. Large spindles with heavy toolholders are not.

Braking resistor sizing

The drive's minimum allowable resistance overrides everything this produces. Enter it from your manual.

Two limits, and which one bites

Lower ohms brake harder — until the drive says otherwise
ResistanceBrakingRisk
Too highWeak — the bus still rises and you still tripNone to the drive; you just do not get the stop you wanted
CorrectEnergy leaves fast enough to hold the bus down—
Too lowStrongMore current than the braking transistor is rated for. This is the failure that costs a drive

So the sequence is: calculate, then check against the drive's stated minimum, then take the higher value. Never the calculated one if it is lower.

Power rating and duty

A resistor's peak power and its continuous rating are different things. Braking is intermittent, so what matters is the average: peak power multiplied by the proportion of time it is actually dissipating. Under-rating shows up as a resistor that glows, smells, and eventually opens — at which point the overvoltage protection is gone and the next fast stop trips the drive.

Two practical notes:

Wiring

If you keep getting overvoltage trips with a resistor fitted, the cause is usually that the demanded stop is faster than the resistor can absorb, or the deceleration time is shorter than the mechanical stop needs. Lengthen the deceleration time before fitting a smaller resistor.

Parts

Braking resistors

Questions

Do I need a braking resistor on a CNC spindle?

Only if you need to stop faster than the spindle coast-stops, or you do rigid tapping and frequent reversals. A router spindle cutting wood or plastic almost never needs one.

Why does the drive trip with overvoltage every time I stop?

The spindle is acting as a generator and pumping its kinetic energy back into the DC bus. Either the deceleration time is too short for the load inertia, or there is nowhere for that energy to go.

Can I use any resistor of the right resistance?

No. The resistance must not be below the minimum your drive allows, and the power rating has to cover the peak braking energy at your duty cycle. Both are maker-specific — take them from your own drive manual. The calculator on this page works out what you need once you have those two limits.

Sources and method

Three kinds of statement appear on this page, and each is labelled where it occurs: